10 A 32 Vac Dual-Element Time-Delay Glass Fuse - Eaton MDQ-10
10 A 32 Vac Dual-Element Time-Delay Glass Fuse - Eaton MDQ-10

10 A 32 Vac Dual-Element Time-Delay Glass Fuse - Eaton MDQ-10

Share
Eaton MDQ-10: 10 A dual-element time-delay glass tube fuse, 32 Vac, 1/4 x 1-1/4 in (6.3 x 32 mm), dual element.
    • Product Details
    • Download

    Eaton MDQ-10 10 A 32 Vac Dual-element time-delay Glass Tube Fuse

    10 A at 32 Vac - dual-element time-delay, glass body, 1/4 x 1-1/4 in, dual element. Breaking capacity 35 A at 250 Vac up to 1 A, 100 A to 7 A, 1,000 A at 32 V above.

    Key Parameters

    Part numberMDQ-10
    Voltage rating32 Vac
    End capsnickel-plated brass
    BodyGlass tube, 1/4 x 1-1/4 in (6.3 x 32 mm)
    Breaking capacity35 A at 250 Vac up to 1 A, 100 A to 7 A, 1,000 A at 32 V above
    Rated current10 A
    Elementdual element
    Typical DC cold resistance0.0072 Ω
    Design standardUL 248-14
    AC interrupting rating1,000 A at 32 Vac

    Decoding the Order Code

    MDQ is the family and 10 is the ampere rating, 10 A. The trailing -R marks the RoHS version; a packaging prefix such as BK- or BK1- may be added in front, which alters the quantity per box only.

    This is the dual-element branch of the family, so the code does not carry a separate suffix for it - the family letter already implies it.

    What the Curve Does

    The construction also makes the part more resistant to cycling. A single-element delay fuse accumulates fatigue every time it is asked to ride a start; a dual-element part transfers that duty to a spring that does not fatigue.

    This Rating in Context

    High-current tube fuses are usually protecting a distribution point rather than a single load, so the rating is set by the cable downstream. Changing the load without re-checking the cable is how a fuse ends up oversized.

    The step below is MDQ-9 at 9 A, the step above is MDQ-15 at 15 A. Between the three the body, the end caps and the breaking capacity are identical; only the element changes, so the choice is the load current and nothing else.

    The Three Figures That Matter

    The secondary columns are where the engineering hides. The typical cold resistance is 0.0072 Ω, which is what the circuit sees before the element warms. The current and voltage ratings only say when they matter.

    Approvals

    UL Listed 1/16-7 A (Guide JDYX, File E19180); UL Recognition 7.5-15 A (JDYX2); CSA (1422-01).

    Note that Listed and Recognised are different claims: Listed means the part is a complete device, Recognised means it is a component for use inside one. Mixing the two in a bill of materials is a common source of confusion at audit.

    Before You Order

    MDQ is a genuine dual-element fuse: one element for the surge, a second for the fault. That is different from a single-element time-delay fuse with a slower curve, and it is why MDQ holds a motor start that would take out an MDL.

    For a like-for-like replacement, match three things: 10 A, dual-element time-delay speed, and a voltage rating at least as high as the circuit can apply. Everything else about the part - the cap plating, the marking, the packaging prefix - is a purchasing detail rather than an electrical one.

  • If the holder is being replaced at the same time, check the clip force. A relaxed clip on a glass tube runs hot and the fuse gets blamed.
  • FAQ

    Is the ampere rating a continuous rating?
    It is the current the fuse will carry indefinitely at 25 °C without opening. In a hot enclosure the usable current is lower, which is why fuses are normally derated to about 75 % of the rating in a sealed box.

    Why is the cold resistance higher on the small ratings?
    The element is thinner and longer relative to its cross-section, so resistance rises as the rating falls. That is also why the smallest ratings dissipate proportionally more and are the ones most affected by a hot enclosure.

    Is the melting I2t the same as the clearing I2t?
    No. The figure in the table is the melting integral - the energy to start the element melting. The clearing integral also includes the arc and is larger. Size downstream parts against clearing, not melting.

    Design note: the ratings above are Technical Data 2044. Verify the exact rating, the voltage at which the breaking capacity applies, and the certificate for this current before release.