170M3494 Eaton Bussmann 1300V 200A Class aR High Speed Fuse
170M3494 Eaton Bussmann 1300V 200A Class aR High Speed Fuse

170M3494 Eaton Bussmann 1300V 200A Class aR High Speed Fuse

Share
Eaton Bussmann 170M3494 — 1300V 200A Class aR high speed fuse, 100 kA interrupting. Protects semiconductors in drives, rectifiers and inverters.
    • Product Details
    • Download

    170M3494 Eaton Bussmann 1300V 200A Class aR High Speed Fuse

    At a Glance
    • 1300 V (UL), 1250 V (IEC) rated voltage, 200 A rated current
    • 100 kA interrupting rating
    • Class aR time-current characteristic

    The Eaton Bussmann 170M3494 is a square body fuse with 1300 V (UL), 1250 V (IEC) rated voltage, 200 A rated current, 100 kA interrupting capacity, carrying a Class aR time-current characteristic.

    Specifications

    General specifications
    UPC051712256292
    EAN5704057022200
    Product Length/Depth59 mm
    Product Height75 mm
    Product Width45 mm
    Product Weight295 g
    Electrical data
    Amperage Rating200 A
    Voltage rating1300 V (UL), 1250 V (IEC)
    Clearing (I2T)31000 at 1000 V 41000 at 1250 V
    Pre arc (I2T)5150
    Watt losses45 W
    Breaking capacity100 kA
    ClassClass aR
    Product specification
    Fuse size1*

    Series Selection Table

    170M3494 series selection table
    Ampere ratings, dimensions and catalog numbers across the Square Body Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Industrial equipment

    Selection Notes

    • Check the voltage rating against the system voltage, and the interrupting rating against the available fault current, before specifying.

    Common Questions

    What are the ratings of the Eaton Bussmann 170M3494?
    1300 V (UL), 1250 V (IEC) / 200 A, with a 100 kA interrupting rating.
    How much fault current can the 170M3494 interrupt?
    100 kA. The available fault current at the installation point must not exceed this value.
    What does Class aR mean for the 170M3494?
    Class aR defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the 170M3494 for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.