170M3957 Eaton Bussmann 1000V 200A Class aR High Speed Fuse
170M3957 Eaton Bussmann 1000V 200A Class aR High Speed Fuse

170M3957 Eaton Bussmann 1000V 200A Class aR High Speed Fuse

Share
Eaton Bussmann 170M3957 — 1000V 200A Class aR high speed fuse, 125 kAIC interrupting. Protects semiconductors in drives, rectifiers and inverters.
    • Product Details
    • Download

    170M3957 Eaton Bussmann 1000V 200A Class aR High Speed Fuse

    At a Glance
    • 1000 V (IEC) rated voltage, 200 A rated current
    • 125 kAIC interrupting rating
    • Class aR time-current characteristic
    • Centre fuse status indicator

    The Eaton Bussmann 170M3957 is a square body fuse with 1000 V (IEC) rated voltage, 200 A rated current, 125 kAIC interrupting capacity, carrying a Class aR time-current characteristic. Construction is centre fuse status indicator.

    Specifications

    General specifications
    EAN5027590450607
    UPC051712678827
    Product Length/Depth152 mm
    Product Height59 mm
    Product Width86 mm
    Product Weight0.36 kg
    Electrical data
    Amperage Rating200 A
    ClassClass aR
    Clearing (I2T)29500 at 1000 V
    Interrupt rating125 kAIC
    Pre arc (I2T)4950
    Voltage rating1000 V (IEC)
    Watt losses50 W
    Product specifications
    ApplicationSemiconductor, DC Common bus, DC drives, power converters/rectifiers
    Fitted with:Type K Indicator for micro
    Fuse indicatorCentre fuse status indicator
    Fuse size1*
    Fuse typeFlush end BKN/Type K Indicator for Micro

    Series Selection Table

    170M3957 series selection table
    Ampere ratings, dimensions and catalog numbers across the Square Body Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Industrial equipment

    Selection Notes

    • Check the voltage rating against the system voltage, and the interrupting rating against the available fault current, before specifying.

    Common Questions

    What are the ratings of the Eaton Bussmann 170M3957?
    1000 V (IEC) / 200 A, with a 125 kAIC interrupting rating.
    How much fault current can the 170M3957 interrupt?
    125 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class aR mean for the 170M3957?
    Class aR defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the 170M3957 for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.