170M4392 Eaton Bussmann 1250V 350A Class aR High Speed Fuse
170M4392 Eaton Bussmann 1250V 350A Class aR High Speed Fuse

170M4392 Eaton Bussmann 1250V 350A Class aR High Speed Fuse

Share
Eaton Bussmann 170M4392 — 1250V 350A Class aR high speed fuse, 100 kAIC interrupting. Protects semiconductors in drives, rectifiers and inverters.
    • Product Details
    • Download

    170M4392 Eaton Bussmann 1250V 350A Class aR High Speed Fuse

    At a Glance
    • 1250 V (IEC), 1300 V (UL) rated voltage, 350 A rated current
    • 100 kAIC interrupting rating
    • Class aR time-current characteristic
    • Centre fuse status indicator

    The Eaton Bussmann 170M4392 is a square body fuse with 1250 V (IEC), 1300 V (UL) rated voltage, 350 A rated current, 100 kAIC interrupting capacity, carrying a Class aR time-current characteristic. Construction is centre fuse status indicator.

    Specifications

    General specifications
    Model CodeFUSE 350A 1250V 1BKN/75 AR CU
    UPC051712258616
    EAN5027590452465
    Product Length/Depth73 mm
    Product Height52 mm
    Product Width170 mm
    Product Weight280.5 g
    Global Catalog170M4392
    Product specifications
    Amperage Rating350 A
    Breaking capacity100 kA
    Fuse indicatorCentre fuse status indicator
    Insulated metal gripping lugs (IMGL)No
    Utilization categoryaR (accompanied semiconductor protection)
    Voltage typeAC/DC
    Fuse size1
    Rated voltage AC1250 V
    Center-to-center distance of connections74.6 mm
    Current typeAC
    Mounting dimensionM8
    ClassClass aR
    Clearing (I2T)125000 at 1000 V, 165000 at 1250 V
    Watt losses70 W
    Fuse shapeSquare body, flush end contacts
    Pre arc (I2T)20000
    ColorNone
    Interrupt rating100 kAIC
    Fitted with:Type K Indicator for micro
    Construction size1
    Mounting methodFlush
    Packaging typeStandard
    Voltage rating1250 V (IEC), 1300 V (UL)
    TypeFuse
    ApplicationSemiconductor, DC Common bus, DC drives, power converters/rectifiers
    Fuse typeFlush end BKN/75 Type K Indicator for Micro
    Fuse system (according to IEC 60269)IEC 60269-4 flush end connections type A

    Series Selection Table

    170M4392 series selection table
    Ampere ratings, dimensions and catalog numbers across the Square Body Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Industrial equipment

    Selection Notes

    • Check the voltage rating against the system voltage, and the interrupting rating against the available fault current, before specifying.

    Common Questions

    What are the ratings of the Eaton Bussmann 170M4392?
    1250 V (IEC), 1300 V (UL) / 350 A, with a 100 kAIC interrupting rating.
    How much fault current can the 170M4392 interrupt?
    100 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class aR mean for the 170M4392?
    Class aR defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the 170M4392 for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.