170M4396 Eaton Bussmann 1000V 550A Class aR High Speed Fuse
170M4396 Eaton Bussmann 1000V 550A Class aR High Speed Fuse

170M4396 Eaton Bussmann 1000V 550A Class aR High Speed Fuse

Share
Eaton Bussmann 170M4396 — 1000V 550A Class aR high speed fuse, 100 kAIC interrupting. Protects semiconductors in drives, rectifiers and inverters.
    • Product Details
    • Download

    170M4396 Eaton Bussmann 1000V 550A Class aR High Speed Fuse

    At a Glance
    • 1000 V (IEC), 1300 V (UL) rated voltage, 550 A rated current
    • 100 kAIC interrupting rating
    • Class aR time-current characteristic
    • Centre fuse status indicator

    The Eaton Bussmann 170M4396 is a square body fuse with 1000 V (IEC), 1300 V (UL) rated voltage, 550 A rated current, 100 kAIC interrupting capacity, carrying a Class aR time-current characteristic. Construction is centre fuse status indicator.

    Specifications

    General specifications
    EAN5027590452557
    UPC051712258654
    Product Length/Depth73 mm
    Product Height52 mm
    Product Width170 mm
    Product Weight556 g
    Electrical data
    Amperage Rating550 A
    ClassClass aR
    Clearing (I2T)465000 at 1000 V, 590000 at 1250 V
    Interrupt rating100 kAIC
    Pre arc (I2T)95000
    Voltage rating1000 V (IEC), 1300 V (UL)
    Watt losses95 W
    Product specifications
    ApplicationSemiconductor, DC Common bus, DC drives, power converters/rectifiers
    Fitted with:Type K Indicator for micro
    Fuse indicatorCentre fuse status indicator
    Fuse size1
    Fuse typeFlush end BKN/75 Type K Indicator for Micro

    Series Selection Table

    170M4396 series selection table
    Ampere ratings, dimensions and catalog numbers across the Square Body Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Industrial equipment

    Selection Notes

    • Check the voltage rating against the system voltage, and the interrupting rating against the available fault current, before specifying.

    Common Questions

    What are the ratings of the Eaton Bussmann 170M4396?
    1000 V (IEC), 1300 V (UL) / 550 A, with a 100 kAIC interrupting rating.
    How much fault current can the 170M4396 interrupt?
    100 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class aR mean for the 170M4396?
    Class aR defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the 170M4396 for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.