170M4497 Eaton Bussmann 1300V 630A Class aR High Speed Fuse
170M4497 Eaton Bussmann 1300V 630A Class aR High Speed Fuse

170M4497 Eaton Bussmann 1300V 630A Class aR High Speed Fuse

Share
Eaton Bussmann 170M4497 — 1300V 630A Class aR high speed fuse, 100 kA interrupting. Protects semiconductors in drives, rectifiers and inverters.
    • Product Details
    • Download

    170M4497 Eaton Bussmann 1300V 630A Class aR High Speed Fuse

    At a Glance
    • 1300 V (UL), 1250 V (IEC) rated voltage, 630 A rated current
    • 100 kA interrupting rating
    • Class aR time-current characteristic

    The Eaton Bussmann 170M4497 is a square body fuse with 1300 V (UL), 1250 V (IEC) rated voltage, 630 A rated current, 100 kA interrupting capacity, carrying a Class aR time-current characteristic.

    Specifications

    General specifications
    UPC051712259095
    EAN5704057026093
    Product Length/Depth69 mm
    Product Height75 mm
    Product Width53 mm
    Product Weight956 g
    Electrical data
    Amperage Rating630 A
    Voltage rating1300 V (UL), 1250 V (IEC)
    Clearing (I2T)660000 at 1000 V
    Pre arc (I2T)130000
    Watt losses110 W
    Breaking capacity100 kA
    ClassClass aR
    Product specification
    Fuse size1

    Series Selection Table

    170M4497 series selection table
    Ampere ratings, dimensions and catalog numbers across the Square Body Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Industrial equipment

    Selection Notes

    • Check the voltage rating against the system voltage, and the interrupting rating against the available fault current, before specifying.

    Common Questions

    What are the ratings of the Eaton Bussmann 170M4497?
    1300 V (UL), 1250 V (IEC) / 630 A, with a 100 kA interrupting rating.
    How much fault current can the 170M4497 interrupt?
    100 kA. The available fault current at the installation point must not exceed this value.
    What does Class aR mean for the 170M4497?
    Class aR defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the 170M4497 for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products