5CLE-400E Eaton Bussmann 4.8kV 400A Class E Medium Voltage Fuse
5CLE-400E Eaton Bussmann 4.8kV 400A Class E Medium Voltage Fuse

5CLE-400E Eaton Bussmann 4.8kV 400A Class E Medium Voltage Fuse

Share
pEaton Bussmann 5CLE-400E, 4.8kV 400A Class E medium voltage fuse, 63 kAIC interrupting. For transformer, feeder and switchgear protection./p
    • Product Details
    • Download

    5CLE-400E Eaton Bussmann 4.8kV 400A Class E Medium Voltage Fuse

    At a Glance
    • 4.8 kV rated voltage, 400 A rated current
    • 63 kAIC interrupting rating
    • Class E time-current characteristic

    The Eaton Bussmann 5CLE-400E is a medium voltage fuse with 4.8 kV rated voltage, 400 A rated current, 63 kAIC interrupting capacity, carrying a Class E time-current characteristic.

    Specifications

    General specifications
    UPC051712528795
    Product Length/Depth17.9 in
    Product Height6.3 in
    Product Width3 in
    Product Weight19 lb
    Electrical rating
    Amperage Rating400 A
    Interrupt rating63 kAIC
    Voltage rating4.8 kV
    General information
    ClassClass E
    Special featuresIndoor/outdoor, double barrel

    Series Selection Table

    5CLE-400E series selection table
    Ampere ratings, dimensions and catalog numbers across the Medium Voltage Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Energy and utility distribution
    • Industrial equipment
    • Transformer protection

    Selection Notes

    • Select against the available fault current at the installation point, not the load current — the interrupting rating has to exceed it with margin.
    • E-rated fuses follow a defined melting curve; pairing them with non-E-rated devices in the same feeder breaks coordination.

    Common Questions

    What are the ratings of the Eaton Bussmann 5CLE-400E?
    4.8 kV / 400 A, with a 63 kAIC interrupting rating.
    How much fault current can the 5CLE-400E interrupt?
    63 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class E mean for the 5CLE-400E?
    Class E defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the 5CLE-400E for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.