| Part number | GMD-630-R |
| AC interrupting rating | 35 A at 250 Vac; 10,000 A at 125 Vac |
| Rated current | 630 mA |
| End caps | nickel-plated brass |
| Typical DC cold resistance | 0.4475 Ω |
| Voltage rating | 250 Vac |
| Body | Glass tube, 5 x 20 mm |
| Element | single element |
| Design standard | UL/CSA 248-14 |
| Typical melting I2t | 3.1 A²s |
| Maximum voltage drop | 450 mV |
The typical cold resistance is 0.4475 Ω, which is what the circuit sees before the element warms. Melting takes 3.1 A²s, so a fault has to deliver that much energy before the element even starts to go. At rated current the drop across it is 450 mV. Those are the figures that decide whether this part fits a circuit, and none of them appears on the label.
In a panel full of motor starters, the delay fuse is what stops the maintenance team from uprating fuses to stop them blowing. The rating stays at the conductor size and the curve absorbs the start.
The code breaks into three parts. GMD is the family, 630 is the ampere rating written in milliamps - which is 630 mA, not 630 amps - and -R is the RoHS suffix. Reading the middle group as amps is the single most common ordering error on this series.
Between a tenth of an amp and one amp the part is protecting a small power supply, a control transformer primary or a fan. This is the volume centre of the range and the rating most often held in stock, which makes it the natural starting point when a circuit has no previous fuse to match.
The step below is GMD-600-R at 600 mA, the step above is GMD-750-R at 750 mA. Between the three the body, the end caps and the breaking capacity are identical; only the element changes, so the choice is the load current and nothing else.
UL Listed (Guide JDYX, File E19180); UL Recognition 4 A (JDYX2); CSA; VDE; SEMKO; PSE; JET.
For a submittal pack, match the certificate to the rating on the order line. Eaton publishes the recognised range alongside each standard, and the boundary between Listed and Recognised often falls inside the family rather than at its end.
GMD is the 5 x 20 mm time-delay part. The IEC holder it sits in is often already on the board, so the choice is usually made by the holder rather than by the circuit - make sure the delay curve is what the load actually needs.
At 630 mA the part is a direct replacement for any other 5 x 20 mm fuse of the same rating and the same speed, regardless of maker. The body size is standardised; the only things that must match are the ampere rating, the speed and the voltage.
Is the ampere rating a continuous rating?
It is the current the fuse will carry indefinitely at 25 °C without opening. In a hot enclosure the usable current is lower, which is why fuses are normally derated to about 75 % of the rating in a sealed box.
What is the difference between 3AG and 3AB?
Both are 1/4 x 1-1/4 in. 3AG is the glass body, 3AB is the ceramic one. The footprint is identical; the breaking capacity is not.
Can I replace a glass fuse with a ceramic one of the same rating?
Yes, and it is usually an upgrade - the ceramic body interrupts a larger fault. Going the other way is what needs checking, because the glass part may not be rated for the fault level the ceramic one was handling.
Design note: the ratings above are Technical Data 2019. Verify the exact rating, the voltage at which the breaking capacity applies, and the certificate for this current before release.

Dimensional drawing and recommended PCB pad layout from the Eaton data sheet. Tolerances and pad dimensions are as printed on the drawing; check the outline against your layout before release.
Shenzhen Gaorunxin Technology Co., Ltd