| Parameter | Rating |
|---|---|
| Part number | ABC-2-R |
| AC interrupting rating | 100 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc |
| Body | Ceramic tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm) |
| Design standard | UL 248-14 |
| Voltage rating, DC | 125 Vdc |
| Voltage rating | 250 Vac |
| Typical voltage drop | 0.31 V |
| Rated current | 2 A |
| End caps | nickel-plated brass |
| Typical DC cold resistance | 0.089 Ω |
| Element | single element |
| Typical melting I2t | 2.167 A²s |
Engineers usually specify it for these duties:
What are the ratings of the ABC-2-R?
2 A continuous at 125 Vdc, interrupting rating 100 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc.
Can the ABC-2-R be used on a higher fault-current circuit?
No — its interrupting rating is 100 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc. Choose a part whose breaking capacity exceeds the prospective fault current.