Eaton ABC-30-R - 30 A Fast-Blow Ceramic Fuse 250 Vac
Eaton ABC-30-R - 30 A Fast-Blow Ceramic Fuse 250 Vac

Eaton ABC-30-R - 30 A Fast-Blow Ceramic Fuse 250 Vac

Share
pEaton ABC-30-R — 30 A, 250 V, fast-acting ceramic cartridge fuse, 200 A at 250 Vac; 1,000 A at 125 Vac; 400 A at 125 Vdc; 1,000 A at 75 Vdc interrupting./p
    • Product Details
    • Download

    Eaton ABC-30-R - 30 A Fast-Blow Ceramic Fuse 250 Vac

    Eaton ABC-30-R - 30 A Fast-Blow Ceramic Fuse 250 Vac belongs to the Eaton range. It carries 30 A, rated 125 Vdc, uses a fast-acting element, in a ceramic body.

    Technical Data

    ParameterRating
    Part numberABC-30-R
    Typical melting I2t1,429 A²s
    Typical DC cold resistance0.002225 Ω
    Elementsingle element
    End capsnickel-plated brass
    Voltage rating, DC125 Vdc
    Rated current30 A
    Design standardUL 248-14
    AC interrupting rating200 A at 250 Vac; 1,000 A at 125 Vac; 400 A at 125 Vdc; 1,000 A at 75 Vdc
    Typical voltage drop0.09 V
    BodyCeramic tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm)
    Voltage rating250 Vac

    Design Notes

    • Interrupting capability is 200 A at 250 Vac; 1,000 A at 125 Vac; 400 A at 125 Vdc; 1,000 A at 75 Vdc — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Ceramic body holds higher breaking capacity than glass at the same footprint.
    • It is the usual choice where prospective fault current is high.
    • Working voltage must stay at or below 125 Vdc; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 30 A to stop nuisance trips — fix the cause instead.

    Where It Is Used

    Typical places this fuse turns up:

    • EV

    Common Questions

    What are the ratings of the ABC-30-R?

    30 A continuous at 125 Vdc, interrupting rating 200 A at 250 Vac; 1,000 A at 125 Vac; 400 A at 125 Vdc; 1,000 A at 75 Vdc.

    Is the ABC-30-R fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    Can the ABC-30-R be used on a higher fault-current circuit?

    No — its interrupting rating is 200 A at 250 Vac; 1,000 A at 125 Vac; 400 A at 125 Vdc; 1,000 A at 75 Vdc. Choose a part whose breaking capacity exceeds the prospective fault current.