Eaton C515-1.25-R 1.25 A 5 x 15 mm Time-Delay Glass Tube Fuse
Eaton C515-1.25-R 1.25 A 5 x 15 mm Time-Delay Glass Tube Fuse

Eaton C515-1.25-R 1.25 A 5 x 15 mm Time-Delay Glass Tube Fuse

Share
pEaton C515-1.25-R — 1.25 A, 250 V, time-delay glass cartridge fuse, 5 x 15 mm, 100 A at 250 Vac; 10000 A at 125 Vac interrupting./p
    • Product Details
    • Download

    Eaton C515-1.25-R 1.25 A 5 x 15 mm Time-Delay Glass Tube Fuse

    The C515-1.25-R from Eaton carries 1.25 A, rated 250 Vac, uses a time-delay element, in a glass body, measuring 5 x 15 mm.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberC515-1.25-R
    Rated current1.25 A
    Voltage rating250 Vac
    Interrupting rating100 A at 250 Vac; 10000 A at 125 Vac
    Typical DC cold resistance0.13 ohm
    Typical melting I2t22.961 A²s
    Max voltage drop at rated current220 mV
    Body5 x 15 mm axial
    TerminalsTinned copper leads
    SpeedTime-Delay (UL 248-14)
    RoHSCompliant (-R suffix)

    Practical Notes

    • Interrupting capability is 100 A at 250 Vac; 10000 A at 125 Vac — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Footprint 5 x 15 mm — check clip or holder compatibility before substitution.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 1.25 A to stop nuisance trips — fix the cause instead.

    Application Scenarios

    Common installation contexts include:

    • surge
    • transformer

    Questions and Answers

    What are the ratings of the C515-1.25-R?

    1.25 A continuous at 250 Vac, interrupting rating 100 A at 250 Vac; 10000 A at 125 Vac.

    Is the C515-1.25-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    What size is the C515-1.25-R?

    It measures 5 x 15 mm. Match the holder or clip to this footprint.

    Can the C515-1.25-R be used on a higher fault-current circuit?

    No — its interrupting rating is 100 A at 250 Vac; 10000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.