Eaton MOV10V420 MOV Disc Varistor 10 mm
Eaton MOV10V420 MOV Disc Varistor 10 mm

Eaton MOV10V420 MOV Disc Varistor 10 mm

Share
MOV10V420: radial leaded metal oxide varistor, 680 V varistor voltage, 560 V working, 1120 V clamp, 150 pF, 75 J.
    • Product Details
    • Download

    Eaton MOV10V420 MOV Disc Varistor 10 mm

    MOV10V420 at a glance: radial leaded metal oxide varistor, 680 V varistor voltage, 560 V working, 1120 V clamp, 150 pF, 75 J.

    Ratings at a Glance

    ParameterValue
    Orderable part numberMOV10V420
    Varistor voltage at 1 mA680 V
    Maximum continuous AC voltage420 Vrms
    Maximum continuous DC voltage560 Vdc
    Clamping voltage1120 V
    Clamping current25 A
    Maximum surge current, 8/20 us2500 A
    Rated power0.4 W
    Typical capacitance at 1 kHz150 pF
    Maximum energy, 10/1000 us75 J
    Maximum body diameter6.5 mm
    Agency recognitioncURus (UL 1449) and TUV
    Package10 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +125 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1287

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    This is a single-shot device in the sense that the joule rating is quoted for one pulse. A surge protector built around a disc survives because the pulses are rare, not because the part is unlimited; the derating curve states how many.

    The clamp column works out at 1.65 times the varistor voltage: 1120 V at the rated current against 680 V at 1 mA. That ratio is what the downstream part has to survive, not the 680 V figure on the label.

    The disc absorbs 75 J in a 10/1000 us pulse and carries 2500 A in an 8/20 us pulse. Those are single shot figures: the same part will take a fraction of the energy repeatedly.

    At 0.4 W continuous rating the body can sit at the working voltage indefinitely. A 20 mm disc handles roughly 150 pF across the line, which matters on a signal-carrying pair but not on a mains input.

    Within the MOV family this is item 29 of 71 in the Eaton catalogue.

    Positioning in the Range

    Keep the leads short and do not sleeve them together: the loop area between the two leads is part of the clamping path, and folding them against each other is what keeps the inductance low.

    • The clamping voltage is quoted at a test current that is far below the surge. At the full 8/20 rating the residual voltage is higher – read the V-I curve.
    • The epoxy coating is the insulation, so the lead bend radius and the mounting clip both matter: a cracked coating at the lead exit is a failure point.

    Frequently Asked Questions

    Are these parts UL recognised?
    Yes, the data sheet lists cURus to UL 1449 and TUV. The file numbers are on the agency page of the data sheet, and they cover the whole family.

    How do I size the disc diameter?
    From the energy, not the current. Estimate the joule content of the surge your source can deliver, add margin for repeated events, and pick the smallest disc that covers it; a larger disc also raises the capacitance across the line.

    Why is the DC rating higher than the AC rating?
    The AC rating is an RMS value, so the peak of the sine is 1.41 times higher. The DC rating is set at that peak plus margin, which is why a 130 Vac part is rated 170 Vdc.