Eaton MOVGT07V170K Integrated MOV GDT Protector
Eaton MOVGT07V170K Integrated MOV GDT Protector

Eaton MOVGT07V170K Integrated MOV GDT Protector

Share
MOVGT07V170K: integrated MOV / GDT device, 1320 V clamp, 5 pF, 19 J.
    • Product Details
    • Download

    Eaton MOVGT07V170K Integrated MOV GDT Protector

    MOVGT07V170K at a glance: integrated MOV / GDT device, 1320 V clamp, 5 pF, 19 J.

    Ratings at a Glance

    ParameterValue
    Orderable part numberMOVGT07V170K
    UL volts140 Vac
    Recommended MCOV180 Vac
    UL MCOV185 Vac
    MOV voltage at 1 mA220(198~242) V
    GDT voltage at 100 V/s600(480~720) V
    Platform voltage at 1000 V/usmax. 390 V
    Peak voltage at 1000 V/usmax. 1320 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us1750 A
    Maximum energy, 10/1000 us19 J
    Capacitance at 1 kHz5 pF
    Package7 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    The part is coordinated so the GDT does not see the continuous line voltage: the MOV holds off the normal operating level and the GDT only fires inside a surge. That is what makes the series connection possible at mains voltages.

    The MOV inside is a 220(198~242) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 390 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 15 of 160 in the Eaton catalogue.

    What This Family Is For

    The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.

    • The series stack needs the MOV to hold off the line at the end of life as well. If the MOV degrades low in voltage the GDT starts to see the line, which is why the withstand count matters.
    • The withstand count is stated at 2 kV / 1 kA because that is the combination the part is certified for. A different waveform changes the count.

    Frequently Asked Questions

    Is the capacitance low enough for a signal line?
    A few picofarads, yes, but this is a mains protector. Its package and its platform voltage are chosen for an input stage, not for a data pair.

    Why put a GDT in series with a MOV?
    The MOV triggers fast and the GDT clamps low. In series the MOV starts the conduction and the GDT carries the current, so the residual voltage is closer to the GDT arc voltage than to the MOV clamp.

    What keeps the GDT from firing on the normal line voltage?
    The MOV holds off the continuous voltage, so the GDT only sees the line when the MOV is conducting. That coordination is what allows the series stack to sit across mains.