Eaton MOVGT07V560K Coordinated MOV + GDT, 1800 V
Eaton MOVGT07V560K Coordinated MOV + GDT, 1800 V

Eaton MOVGT07V560K Coordinated MOV + GDT, 1800 V

Share
MOVGT07V560K: integrated MOV / GDT device, 1800 V clamp, 5 pF, 64 J.
    • Product Details
    • Download

    Eaton MOVGT07V560K Coordinated MOV + GDT, 1800 V

    MOVGT07V560K at a glance: integrated MOV / GDT device, 1800 V clamp, 5 pF, 64 J.

    Ratings at a Glance

    ParameterValue
    Orderable part numberMOVGT07V560K
    UL volts460 Vac
    Recommended MCOV560 Vac
    UL MCOV600 Vac
    MOV voltage at 1 mA750(675~825) V
    GDT voltage at 100 V/s1000(800~1200) V
    Platform voltage at 1000 V/usmax. 1320 V
    Peak voltage at 1000 V/usmax. 1800 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us1750 A
    Maximum energy, 10/1000 us64 J
    Capacitance at 1 kHz5 pF
    Package7 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    Reading the Data Sheet

    The MOV part of the stack still does the continuous work: it holds the line voltage off the GDT and takes the first microseconds of the surge. The GDT takes over once the gap breaks down.

    The MOV inside is a 750(675~825) V part and the GDT is a 1000(800~1200) V tube. In series the pair holds the surge at the platform voltage of 1320 V, well under the peak 1800 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 40 of 160 in the Eaton catalogue.

    Series Positioning

    Mount it away from the signal ground reference. The GDT arc couples noise into anything nearby, and the platform voltage appears across the package during the event.

    • A GDT has a statistical sparkover. The tolerance in the table is the spread over many units, not the repeatability of one unit.
    • The MOV inside is a disc, so the energy rating follows the disc diameter; the GDT adds current capability, not joules.

    Frequently Asked Questions

    Is the capacitance low enough for a signal line?
    A few picofarads, yes, but this is a mains protector. Its package and its platform voltage are chosen for an input stage, not for a data pair.

    Why put a GDT in series with a MOV?
    The MOV triggers fast and the GDT clamps low. In series the MOV starts the conduction and the GDT carries the current, so the residual voltage is closer to the GDT arc voltage than to the MOV clamp.

    What keeps the GDT from firing on the normal line voltage?
    The MOV holds off the continuous voltage, so the GDT only sees the line when the MOV is conducting. That coordination is what allows the series stack to sit across mains.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message