| Parameter | Value |
|---|---|
| Orderable part number | MOVGT14V270K |
| UL volts | 230 Vac |
| Recommended MCOV | 270 Vac |
| UL MCOV | 300 Vac |
| MOV voltage at 1 mA | 360(324~396) V |
| GDT voltage at 100 V/s | 600(480~720) V |
| Platform voltage at 1000 V/us | max. 640 V |
| Peak voltage at 1000 V/us | max. 1320 V |
| Withstand count at 2 kV / 1 kA | 40 shots |
| MOV withstand current, 8/20 us | 6000 A |
| Maximum energy, 10/1000 us | 130 J |
| Capacitance at 1 kHz | 5 pF |
| Package | 14 mm disc |
| Mounting | Radial, through-hole |
| Operating temperature | -40 °C to +105 °C |
| Qualification | Commercial grade |
| RoHS | Compliant, halogen free |
| Data sheet | Eaton Technical Data ELX1161 |
Dimensions, recommended pad or hole pattern and the derating curves are
on the data sheet pages; the package line above gives the body size as Eaton states it.
This is a mains-input protector, not a board-level one. It is chosen for the first stage ahead of a differential filter, and its platform voltage is what the downstream 1 kV-rated parts have to survive.
The MOV inside is a 360(324~396) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 640 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.
Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.
Within the MOVGT family this is item 105 of 160 in the Eaton catalogue.
Mount it away from the signal ground reference. The GDT arc couples noise into anything nearby, and the platform voltage appears across the package during the event.
Can it be used on DC?
No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.
What is the platform voltage?
It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.
What is the difference between UL volts and MCOV?
UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd