| Parameter | Value |
|---|---|
| Orderable part number | MOVTP14V150T |
| Working voltage, DC | 200 Vdc |
| Working voltage, AC | 150 Vac |
| Varistor voltage at 1 mA | 216 V to 264 V |
| Clamping voltage, 8/20 us | 395 V at 50 A |
| Energy absorption, 10/1000 us | 94 J |
| Rated power | 0.6 W |
| Peak current, 8/20 us | 6000 A |
| Impulse response time | under 25 ns |
| Leakage current at 0.75 V1mA | max. 20 uA |
| Pin form | 3-lead, status contact on the third pin |
| Package | 14 mm disc |
| Mounting | Radial, through-hole |
| Operating temperature | -40 °C to +105 °C |
| Qualification | Commercial grade |
| RoHS | Compliant, halogen free |
| Data sheet | Eaton Technical Data ELX1079 |
Dimensions, recommended pad or hole pattern and the derating curves are
on the data sheet pages; the package line above gives the body size as Eaton states it.
The electrical ratings match an unprotected part of the same disc size, so the selection is unchanged. What changes is the space around the part: the thermal element needs clearance and the third lead needs a route.
The clamp column works out at 1.65 times the varistor voltage: 395 V at the rated current against 240 V at 1 mA. That ratio is what the downstream part has to survive, not the 240 V figure on the label.
Standing at 200 V the leakage is at most 20 uA, which is 4 mW of continuous dissipation. Small, but it is why a varistor on a battery rail has to be chosen on leakage and not only on voltage.
The thermal element is the difference from a plain disc of the same rating. If the body overheats the element opens at 0.6 W of continuous overload, before the epoxy and the board around it are damaged.
The 3-lead form is the mechanical difference: the third pin brings the thermal contact out for monitoring. The electrical table is identical for both.
Within the MOVTP family this is item 4 of 28 in the Eaton catalogue.
In the three-lead version the third pin should be treated as a low-voltage signal: it is isolated from the line, but it runs close to it, so keep the creepage of the monitoring track in mind.
Is the electrical rating different from an unprotected MOV?
No, the disc inside is the same. The thermal element adds series resistance of a few milliohms and takes space, but the voltage and energy ratings are unchanged.
How fast does it trip?
The thermal path takes seconds, not microseconds. It is designed for the overload that follows a shorted varistor, not for the surge itself – the surge is handled by the disc.
Does the third lead carry current?
No. It is a signal contact rated for a monitoring circuit, typically a few milliamps at low voltage. It should not be used to carry the load current.