Eaton MOVTP14V300T MOVTP Varistor with Thermal Fuse
Eaton MOVTP14V300T MOVTP Varistor with Thermal Fuse

Eaton MOVTP14V300T MOVTP Varistor with Thermal Fuse

Share
MOVTP14V300T: thermally protected metal oxide varistor, 423-517 V varistor voltage, 385 V working, 775 V clamp, 192 J.
    • Product Details
    • Download

    Eaton MOVTP14V300T MOVTP Varistor with Thermal Fuse

    MOVTP14V300T at a glance: thermally protected metal oxide varistor, 423-517 V varistor voltage, 385 V working, 775 V clamp, 192 J.

    Specification Table

    ParameterValue
    Orderable part numberMOVTP14V300T
    Working voltage, DC385 Vdc
    Working voltage, AC300 Vac
    Varistor voltage at 1 mA423 V to 517 V
    Clamping voltage, 8/20 us775 V at 50 A
    Energy absorption, 10/1000 us192 J
    Rated power0.6 W
    Peak current, 8/20 us6000 A
    Impulse response timeunder 25 ns
    Leakage current at 0.75 V1mAmax. 20 uA
    Pin form3-lead, status contact on the third pin
    Package14 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1079

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    The element is thermally coupled to the body, not to the current. That distinction matters: a slow overload that heats the disc without a large current still trips it, which a fuse in series would not see.

    The clamp column works out at 1.65 times the varistor voltage: 775 V at the rated current against 470 V at 1 mA. That ratio is what the downstream part has to survive, not the 470 V figure on the label.

    Standing at 385 V the leakage is at most 20 uA, which is 7.7 mW of continuous dissipation. Small, but it is why a varistor on a battery rail has to be chosen on leakage and not only on voltage.

    The thermal element is the difference from a plain disc of the same rating. If the body overheats the element opens at 0.6 W of continuous overload, before the epoxy and the board around it are damaged.

    The 3-lead form is the mechanical difference: the third pin brings the thermal contact out for monitoring. The electrical table is identical for both.

    Within the MOVTP family this is item 10 of 28 in the Eaton catalogue.

    Positioning in the Range

    In the three-lead version the third pin should be treated as a low-voltage signal: it is isolated from the line, but it runs close to it, so keep the creepage of the monitoring track in mind.

    • The third lead is not a second ground. Wiring it to the return defeats the monitoring function and can hold the thermal contact closed.
    • Agency recognition covers the varistor; the thermal element is part of the same approval and does not need a separate file.

    Frequently Asked Questions

    Does the third lead carry current?
    No. It is a signal contact rated for a monitoring circuit, typically a few milliamps at low voltage. It should not be used to carry the load current.

    Can it be used on a DC input?
    The varistor part can, within its DC rating. The thermal element does not care about the waveform, so the DC limitation is the same as for any MOV: the follow current has no zero crossing.

    What approvals does it carry?
    The data sheet lists the agency file for the family. The thermal element is covered by the same approval as the varistor inside.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd