Eaton S520-20-R 20 A 420 Vac Fast-Acting Ceramic Tube Fuse
Eaton S520-20-R 20 A 420 Vac Fast-Acting Ceramic Tube Fuse

Eaton S520-20-R 20 A 420 Vac Fast-Acting Ceramic Tube Fuse

Share
pEaton S520-20-R — 20 A, 420 V, fast-acting ceramic cartridge fuse, 1500 A interrupting./p
    • Product Details
    • Download

    Eaton S520-20-R 20 A 420 Vac Fast-Acting Ceramic Tube Fuse

    Built by Eaton, the S520-20-R carries 20 A, rated 420 Vac, uses a fast-acting element, in a ceramic body.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberS520-20-R (BK- = 100 pcs carton, BK1- = 1,000 pcs polybag; S520-V-20-R for axial leads)
    Interrupting rating at 250 Vac1500 A
    Typical melting I2t420 A2s (measured at 10 In)
    Construction5 x 20 mm ceramic tube, nickel/silver plated brass ends
    Dissipated power at rating4.10 W
    Typical DC cold resistance5 mOhm
    Operating temperature-55 C to +125 C with derating
    Typical voltage drop205 mV at rated current
    Interrupting rating at 420 Vac300 A
    Voltage rating420 Vac
    Current rating20 A
    AgencyUR E19180 (JDYX2); TUV T 50484820 02

    Selection Notes

    • Interrupting capability is 1500 A — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Ceramic body holds higher breaking capacity than glass at the same footprint.
    • It is the usual choice where prospective fault current is high.
    • Working voltage must stay at or below 420 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 20 A to stop nuisance trips — fix the cause instead.

    Typical Applications

    Engineers usually specify it for these duties:

    • PFC
    • surge

    Q&A

    What are the ratings of the S520-20-R?

    20 A continuous at 420 Vac, interrupting rating 1500 A.

    Is the S520-20-R fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    Can the S520-20-R be used on a higher fault-current circuit?

    No — its interrupting rating is 1500 A. Choose a part whose breaking capacity exceeds the prospective fault current.