FWH-450A Eaton Bussmann 450A High Speed Fuse
FWH-450A Eaton Bussmann 450A High Speed Fuse

FWH-450A Eaton Bussmann 450A High Speed Fuse

Share
Eaton Bussmann FWH-450A — 450A high speed fuse, 50 kAIC at 500 Vdc 200 kAIC at 1000 Vac interrupting. Protects semiconductors in drives, rectifiers and inverters.
    • Product Details
    • Download

    FWH-450A Eaton Bussmann 450A High Speed Fuse

    At a Glance
    • 750 Vac, 750 Vdc rated voltage, 450A RMS rated current
    • 50 kAIC at 500 Vdc 200 kAIC at 1000 Vac interrupting rating
    • Blade end x blade end terminations
    • Non Indicating

    The Eaton Bussmann FWH-450A is a high speed fuse with 750 Vac, 750 Vdc rated voltage, 450A RMS rated current, 50 kAIC at 500 Vdc 200 kAIC at 1000 Vac interrupting capacity. Construction is non indicating.

    Specifications

    General specifications
    UPC051712150194
    Product Length/Depth2.17 in
    Product Height2.8 in
    Product Width5.3 in
    Product Weight0.92 lb
    Electrical rating
    Amperage Rating450A RMS
    Interrupt rating50 kAIC at 500 Vdc 200 kAIC at 1000 Vac
    Voltage rating750 Vac, 750 Vdc
    Watt losses74 W
    Physical details
    Packaging typeStandard
    General information
    ConnectionBlade end x blade end
    Fuse indicatorNon Indicating
    Mounting methodStud

    Series Selection Table

    FWH-450A series selection table
    Ampere ratings, dimensions and catalog numbers across the High Speed Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Industrial equipment

    Selection Notes

    • Semiconductor fuses are chosen on I²t let-through against the device surge rating, not on continuous current alone.
    • Termination: Blade end x blade end. Confirm the mating clip or busbar before ordering; ferrule and blade ends are not interchangeable.

    Common Questions

    What are the ratings of the Eaton Bussmann FWH-450A?
    750 Vac, 750 Vdc / 450A RMS, with a 50 kAIC at 500 Vdc 200 kAIC at 1000 Vac interrupting rating.
    How much fault current can the FWH-450A interrupt?
    50 kAIC at 500 Vdc 200 kAIC at 1000 Vac. The available fault current at the installation point must not exceed this value.
    How does the FWH-450A connect?
    Blade end x blade end. Confirm the mating clip, holder or busbar before ordering — ferrule and blade ends are not interchangeable.
    How should I select the FWH-450A for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.