JCY-15E Eaton Bussmann 5500V 15A Class E Medium Voltage Fuse
JCY-15E Eaton Bussmann 5500V 15A Class E Medium Voltage Fuse

JCY-15E Eaton Bussmann 5500V 15A Class E Medium Voltage Fuse

Share
pEaton Bussmann JCY-15E, 5500V 15A Class E medium voltage fuse, 60 kAIC interrupting. For transformer, feeder and switchgear protection./p
    • Product Details
    • Download

    JCY-15E Eaton Bussmann 5500V 15A Class E Medium Voltage Fuse

    At a Glance
    • 5500 V rated voltage, 15 A rated current
    • 60 kAIC interrupting rating
    • Class E time-current characteristic
    • Single element

    The Eaton Bussmann JCY-15E is a fuse with 5500 V rated voltage, 15 A rated current, 60 kAIC interrupting capacity, carrying a Class E time-current characteristic. Construction is 1 barrel, non indicating.

    Specifications

    General specifications
    UPC051712694476
    Product Length/Depth3.5 in
    Product Height11.5 in
    Product Width3.5 in
    Product Weight3.45 lb
    Electrical rating
    Amperage Rating15 A
    Interrupt rating60 kAIC
    Voltage rating5500 V
    Physical details
    Packaging typeStandard
    General information
    Barrels1
    ClassClass E
    ConnectionFerrule end x ferrule end
    ElementSingle
    Fuse indicatorNon Indicating

    Series Selection Table

    JCY-15E series selection table
    Ampere ratings, dimensions and catalog numbers across the Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Energy and utility distribution
    • Industrial equipment
    • Photovoltaic systems

    Selection Notes

    • Termination: Ferrule end x ferrule end. Confirm the mating clip or busbar before ordering; ferrule and blade ends are not interchangeable.

    Common Questions

    What are the ratings of the Eaton Bussmann JCY-15E?
    5500 V / 15 A, with a 60 kAIC interrupting rating.
    How much fault current can the JCY-15E interrupt?
    60 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class E mean for the JCY-15E?
    Class E defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How does the JCY-15E connect?
    Ferrule end x ferrule end. Confirm the mating clip, holder or busbar before ordering — ferrule and blade ends are not interchangeable.
    How should I select the JCY-15E for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.