PV-2A10F Eaton Bussmann 1000V 2A Class gPV Fuse
PV-2A10F Eaton Bussmann 1000V 2A Class gPV Fuse

PV-2A10F Eaton Bussmann 1000V 2A Class gPV Fuse

Share
Eaton Bussmann PV-2A10F — 1000V 2A Class gPV fuse, 50 kAIC interrupting.
    • Product Details
    • Download

    PV-2A10F Eaton Bussmann 1000V 2A Class gPV Fuse

    At a Glance
    • 1000 Vdc rated voltage, 2 A rated current
    • 50 kAIC interrupting rating
    • Class gPV time-current characteristic
    • Other

    The Eaton Bussmann PV-2A10F is a fuse with 1000 Vdc rated voltage, 2 A rated current, 50 kAIC interrupting capacity, carrying a Class gPV time-current characteristic. Construction is other.

    Specifications

    General specifications
    Model Code2A 1000V DC SOLAR FERRULE 10x38mm
    UPC051712245173
    EAN5027590505970
    Product Length/Depth38 mm
    Product Height10 mm
    Product Width10 mm
    Product Weight9.8 g
    Electrical rating
    Amperage Rating2 A
    Voltage rating1000 Vdc
    Interrupt rating50 kAIC
    ClassClass gPV
    Pre arc (I2T)1.2
    Watt losses0.6 W
    Product specifications
    ApplicationCombiner boxes, inverters, pv wire harnesses, Photovoltaic strings
    Fuse typePV-A10F
    Fuse indicatorOther
    Fuse size10 x 38 mm
    Quantity10
    Compatible fuse holder
    Suitable forCHPV Modular fuse holder HPV-DV Inline holder

    Standards Reference

    • IEC 60269-6

    Series Selection Table

    PV-2A10F series selection table
    Ampere ratings, dimensions and catalog numbers across the Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Industrial equipment

    Selection Notes

    • Check the voltage rating against the system voltage, and the interrupting rating against the available fault current, before specifying.

    Common Questions

    What are the ratings of the Eaton Bussmann PV-2A10F?
    1000 Vdc / 2 A, with a 50 kAIC interrupting rating.
    How much fault current can the PV-2A10F interrupt?
    50 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class gPV mean for the PV-2A10F?
    Class gPV defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    Which standards does the PV-2A10F comply with?
    It is referenced against IEC 60269-6 in the manufacturer data.
    How should I select the PV-2A10F for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.